Descarga la aplicación para disfrutar aún más
Vista previa del material en texto
Copyright © 2005, ASHRAE ASHRAE HANDBOOK Additions and Corrections This report includes additional information and technical errors To cool from 18 to 4°C in a chilled room: found between June 15, 2002, and April 1, 2005, in the SI editions of the 2002, 2003, and 2004 ASHRAE Handbook volumes. Occa- sional typographical errors and nonstandard symbol labels will be corrected in future volumes. The most current list of Handbook addi- tions and corrections is on the ASHRAE Web site (www.ashrae.org). The authors and editor encourage you to notify them if you find other technical errors. Please send corrections to: Handbook Editor, ASHRAE, 1791 Tullie Circle NE, Atlanta, GA 30329, or e-mail mowen@ashrae.org. 2002 Refrigeration p. 2.2, Figs. 1 and 2. In the captions, replace “ton of refrigeration” with “kilowatt of refrigeration.” p. 2.4, Example 1, Solution. The correct calculations are as follows: p. 2.10, 2nd col. In the first sentence under Refrigerant Line Capacity Tables, replace “tons of refrigeration” with “kilowatts of refrigeration.” p. 2.16, Example 2. In the Solution, the reference to Table 10 should be to Table 16. p. 8.5, Table 3. The specific heats above and below freezing for bacon should both be 2.70 kJ/(kg·K); for whole cured lean ham they should be 3.47 and 2.22 kJ/(kg·K), respectively. p. 8.8, Eq. (18). The equation should read as follows: p. 8.9, 2nd col., 3rd equation. Delete the 3 directly to the right of the equals sign. p. 10.9, Table 2. Delete the entry for “Maple syrup.” p. 12.1, 1st col., 5th line from bottom. Change “15 mph” to “25 km/h.” p. 12.1, 2nd col. In the first full paragraph, change “These values decrease” to “These values increase.” p. 12.2, Example 1. The solution should be as follows: Specific heat of beef before freezing is listed in Table 3, Chapter 8 as 3.52 kJ/(kg · K); after freezing, 2.12 kJ/(kg · K). Actual temperature drop = (50 × 0.02) × (14.0/21.54)1.8 = 0.46 K Estimated friction loss = 0.46 (50 × 0.749) = 17.2 kPa Loss for the riser = 6 × 11.3 = 67.8 kPa Total pressure losses = 67.8 + 17.2 = 85.0 kPa Saturation pressure at 40°C condensing (see R-22 properties in Chapter 20, 2001 ASHRAE Handbook—Fundamentals) = 1534.1 kPa Initial pressure at beginning of liquid line 1534.1 kPa Total liquid line losses − 85.0 kPa Net pressure at expansion device = 1449.1 kPa The saturation temperature at 1449.1 kPa is 37.7°C. Required subcooling to overcome the liquid losses = (40.0 – 37.7) or 2.3 K H t tr–( ) 1.55 1.26xs xwa xb–( )Lotf trt ----------------------------------–+⎝ ⎠ ⎛ ⎞= A 100 × 3.52(18 − 4) = 4928 kJ To cool from 4°C to freezing point in freezer: 100 × 3.52[4 − (−2)] = 2112 kJ To freeze: 100 × 233 = 23 300 kJ To cool from freezing to storage temperature: 100 × 2.12[(−2) − (−18)] = 3392 kJ Total: 4928 + 2112 + 23 300 + 3392 = 33 732 kJ p. 12.7, Infiltration Load values. Delete “°C” from the definitions for hf, hr, and ρr; for ρi, the entire definition should read only “den- sity incoming air, kg/m3.” p. 16.10, 2nd col. The next to the last sentence under Fresh Pork Holding should read, “Care must be taken to maintain the ratio of kilograms of CO2 to kilograms of meat for the retention period.” p. 7.14, Fig. 17. The viscosity data are for 38°C, in mm2/s. p. 22.7, Airflow Requirements. The units for cp should be J/(kg·K), and the symbol for mass flow rate of air should be . p. 25.2, 16th line. Change “metre” to “cubic metre.” p. 30.2, Controls. Change “several hundred feet” to “hundreds of metres.” p. 31.3, 2nd col., 4th line. The text in parentheses should read “(i.e., a total area of 3.0 m2 and a capacity of 0.33 m3).” p. 34.3, Example 2 values. Change the unit for Ceiling radiating area from “mm2” to “m2.” p. 38.21, Fig. 30. Along the x axis, change “100” to “102.” p. I.30, Index. Add the following entry after Load coefficients: Louvers, F30.45 sizing, F34.17-18 2003 HVAC Applications p. 1.4, Evaporative Cooling. The reference to Chapter 50 should be to Chapter 51. p. 8.2, Indoor Air Quality, 4th line. Delete “by a minimum of 1.5 K.” p. 9.2, Power Consumption and Availability. Change “to main- tain gas mileage” to “for minimum vehicle fuel use.” p. 13.6. Reverse the order of Figures 6 and 7. p. 13.10, Example 1. The unit for total floor area should be m2. p. 16.9, Semiconductor Cleanrooms, 1st paragraph. Insert “(0.0283 m3)” after “cubic foot.” p. 16.10, Airflow in Semiconductor Cleanrooms, 4th para- graph. Change “horsepower” to “kilowatt.” p. 16.13, Temperature and Humidity, 3rd paragraph. If full- coverage smocks are not used, temperature set points can be higher, not lower. Ch. 17. This chapter has been reassigned to TC 9.9, which recom- mends using ASHRAE’s Thermal Guidelines for Data Processing Environments (2004) as a primary source of information for data processing environment design. m· .1 A.2 2005 ASHRAE Handbook—Fundamentals (SI) p. 23.7, Fig. 8. The bottom part of the figure was cut off; refer to the full version here. p. 26.7, 2nd line from bottom. Change “only a very few grains of moisture” to “very little moisture.” p. 27.2, Adiabatic Compression. In the second paragraph, change “1.84W” to “1.884W.” In the definitions for Equation (1), units for E should be 1 kJ/(102 m·kg). In Example 1, units for the solution should be kW. p. 27.6. Step 6 should read, “The enthalpy of air hai at 28°C satu- rated and 104.983 kPa is 109 kJ/kg. Σai = 109 – (4.1868)(0.037) (28) = 104.66 kJ/kg.” p. 27.10, 2nd col., 5th full paragraph. Change “calorific” to “heat.” In Equation (18), change “Btu/h” to “kW.” p. 27.11, Eq. (19). Rt should be turbulent resistance. p. 31.5, Type II Hoods, Condensate hood. The second and third sen- tences for this item should read, “The hood is designed to direct the condensate toward a perimeter gutter for collection and drainage, allowing none to drip onto the appliance below. Flow rates are typi- cally based on 255 to 380 L/s per square metre of hood opening.” p. 31.11, Traditional Registers. Terminal velocities should be ≤0.25 m/s. p. 32.4, 2nd col., last paragraph. In the second sentence, velocity should be limited to a maximum of 0.03 m/s. p. 32.6, 2nd col., 4th paragraph. Change “flashing” to “flushing.” The units for free residual chlorine content should be mg/kg. p. 33.22, 1st col. In the third line under Equation (38), change “KJ” to “kJ.” p. 34.2, Lower Initial Cost, 3rd paragraph. Change “660 W” to “660 kW.” Fig. 8 Grain Recirculators Convert Bin Dryer to High-Speed Continuous-Flow Dryer (2003 HVAC Applications, Chapter 23, p. 7) p. 36.3, Table 3. Add the following footnote: 3. For updated information on heat pump life, see Lovvorn and Hiller (2002). p. 36.9, 1st column, 3rd line. The subscript for PWF should be “ser.” p. 36.13, References. Add the following source after Lovvorn and Hiller (1985): Lovvorn, N.C. and C.C. Hiller. 2002. Heat pump life revisited. ASHRAE Transactions 108(2):107-112. p. 41.28, Case Study, 2nd paragraph. Change “3200 KW” to “3200 kW.” p. 45.6, 2nd col., end of 1st paragraph. The correct Research Project is RP-1134 (Tompkins 2002). p. 45.13, References. Delete Idem 2002 and insert the following source after Sterling and Kabayashi 1981: Tompkins, D. 2002. Evaluation of photocatalytic air cleaning capability. ASHRAE Research Project RP-1134. p. 47.15, Tables 8 and 9. The titles for Tables 8 and 9 should read “with 25 mm Fiberglass Lining” and “with 50 mm Fiberglass Lin- ing,” respectively. p. 47.22, Table 22. In the footnote, change “1.5 pcf” to “24 kg/m3.” p. 47.23, Ex. 3. Change “5 ft” to “1.52 m.” p. 47.41, 1st col., 3rd paragraph. Change “12 m/s” to “1.2 m/s.” p. 49.6, Fig. 7. The arrow for “Union (typical)” should point to the union symbol, not the gate valve symbol. The correct figure is pre- sented here. p. 50.1, Snow-Melting Heat Flux Requirement. The fourth list item should be “wind speed near the heated surface.” p. 51.7, Cooling Large Motors,3rd paragraph. Delete “hour” after “kilowatt.” p. 53.3, Fig. 3. Delete the entire note below the figure. p. 53.9, Symbols. Delete the entries for “clo” and “met.” p. 54.4, Eqs. (7) and (8). In the definitions for Wp, delete “in new- tons = mass.” p. 54.12, 1st col., 4th line from bottom. Change “??°C” to “590°C.” p. I.4, Index. Add “F15.12” to the entries for BAS and Building automation system. 2004 HVAC Systems and Equipment p. 2.5, Fig. 8. The caption for Figure 9 should read “Chemical Dehumidification.” p. 6.7, Table 1. The complete table is supplied here. Fig. 7 Reverse/Return Manifold Systems (2003 HVAC Applications, Chapter 49, p. 6) Additions and Corrections A.3 p. 7.22, 1st col., 13th line from bottom. Change “horsepower” to “power.” p. 7.23, Turbocharger Heat Recovery. Delete “(280 kJ/kWh).” p. 8.5, Fig. 5. The top two figures, for air/air and water/air refriger- ant changeover, were cut off. The two figures are provided here. Table 1 Thermal Resistance of Ceiling Panels (2004 HVAC Systems and Equipment, Ch. 6, p. 7) Thermal Resistance Type of Panel rp , (m2·K)/W rs , (m2·K)/W 0.32 0.38 0.10 ≤ 0.12 xp kp ----- xp kp ----- xp kp ----- xp Do /– 2 kp ----------------------- 0≈ xp Do /– 2 kp ----------------------- p. 12.9, Fig. 16. The figure for reverse-return two-pipe systems was incorrect; the corrected version is provided here. p. 24.2, 1st two lines. Change “15 to 35 cfm” to “7 to 16.5 L/s,” and “15 cfm” to “7 L/s.” p. 25.4, Eq. (5). There should be an equals symbol after Dpc. p. 25.21, Tables 8 and 9. Delete “g·” from the units for KGa. p. 31.3, 2nd equation. The unit for qc should be W. p. 34.31, Symbols. Delete the definition for gc. p. 35.19, Purging, 2nd paragraph. Change “Chapters 35 and 38 of this volume” to “Chapter 38 of this volume.” p. 36.4, Fig. 9. Change “350 to 500 ft” to “100 to 150 m.” p. 36.14, Fig. 25. The corrected figure is supplied on p. A.4. p. 44.10, Fig. 5. Replace with the corrected figure, supplied on p. A.4. Fig. 16 Direct- and Reverse-Return Two-Pipe Systems (2004 HVAC Systems and Equipment, Ch. 12, p. 9) Fig. 5 Heat Pump Types (first two rows) (2004 HVAC Systems and Equipment, Ch. 8, p. 5) A.4 2005 ASHRAE Handbook—Fundamentals (SI) p. 44.19, Ex. 4, Step 7. The reference to Figure 17 should be to Fig- ure 19. p. 44.25, Bibliography. The correct entry for the ASHRAE (1974) source is as follows: ASHRAE. 1974. Symposium on heat recovery. ASHRAE Transactions 80(1):302-332. Index. The following are the correct page numbers for these entries: Compressors, heat pump systems, S8.6 Control, heat recovery systems, S8.18 Defrosting, air-source heat pump coils, S8.7, 8; S45.9 Heat balance (HB), studies, S8,19 Heat pumps (all subentries with S1 should be S8) Heat recovery (all subentries with S1 should be S8) Fig. 5 Variation of Pressure Drop and Effectiveness with Air Flow Rates for a Membrane Plate Exchanger (2004 HVAC Systems and Equipment, Ch. 44, p. 10) Industrial applications, heat pumps, S8.8 Net positive suction, S39.9 Refrigerant control devices, R45 heat pumps, system, S8.7 Solar energy, heat pump systems, S8.4 Fig. 25 Cooling Tower Performance—167% Design Flow (2004 HVAC Systems and Equipment, Ch. 36. p. 14) Main Menu SI Table of Contents Search ...entire edition ...this document Help 2002 Refrigeration 2003 HVAC Applications Fig. 7 Reverse/Return Manifold Systems Fig. 8 Grain Recirculators Convert Bin Dryer to High-Speed Continuous-Flow Dryer 2004 HVAC Systems and Equipment Table 1 Thermal Resistance of Ceiling Panels Fig. 16 Direct- and Reverse-Return Two-Pipe Systems Fig. 5 Heat Pump Types (first two rows) Fig. 5 Variation of Pressure Drop and Effectiveness with Air Flow Rates for a Membrane Plate Exchanger Fig. 25 Cooling Tower Performance-167% Design Flow
Compartir