MEDIDOR CFE.
TRIFASICO 
3F-4H DE 7 
MORDASAS
CON CONEXION A 
TIERRA 
BARILLA 
COPPERWELD 3/4 
1-8 AWG VERDE
B
A
R
R
A
 D
E
 
T
IE
R
R
A
S
 
TERMOAGNETICO
PRINCIPAL
 LAL26300 
 3X300A
In=277
220V
TERMOMGANETICO 
QO240
1X40
In=.30
220V
In=366A
Ic=456.32A
3F-4H
L=10
%e=0.3%
CABLE XHHW-2 600V
600KCMIL
304,0 MM2
PLANTA DE 
EMERGENCIA 
187KVA
EM BEMAC 2 ,SELMEC 
3F-4H TABLERO DE 
EMERGENCIA (PARA 
BOMBA CONTRA 
INCENDIOS)
NF303AB62*
DE 6000A 
3F-4H
PARA 30 CIRCUTOS 
MONOFASICOS
NOTA: ALUMBRADO 
DE EMERGENCIA Y 
CONTACTOS A 
FUTURO
M M M
ITM PRINCIPAL
NAL26900
 3X900A
CAPACIDAD DE 
CABLE 600KCMIL
200 HP TRIFASICO 
(BOMBA CONTRA 
INCENDIOS)
IN=277A
PN=150000WATTS
30 HP 
TRIFASICO
IN=59A
PN=22371WATTS
10 HP MONOFASICO
IN=30A
PN=7457WATTS
 GABINETE PARA 
ITM 
P1200FMX
 3X700
In=277A
LISTA DE MATERIALES 
•TUBERIA CONDUIT 2" ,1 1/4 ",3/4
•COPLES 2" ,1 1/4 ",3/4
•CONECTORES2",1 1/4 ",3/4
•ABRAZADERAS 2",1 1/4 ",3/4
•ESPARRAGO 3/8
•TUERCAS 3/8
•RONDANAS 3/8
•UNICANAL 4X4CM
•ZAPATA MECANICA O MOLDE PARASOLDAR
•TUBERIA 
•CABLE CALIBRE 6 AWG 
•CABLE CALIBRE 10 AWG
•CABLE CALIBRE 250 KCMI
•ABLE CALIBRE XHHW 600KCMIL 
NOTAS IMPORTANTES 
LA CONSTRUCCION DE ESTA INSTALACION SE 
HIZO SIGUIENDO LA NOM-001-SEDE-2012
LA INSTALACION DE CABLEADO TOMANDO EN 
CUENTA LA TABLA DE AMPACIDAD 310-15(B)(16)
PARA LOS MOTORES SE TOMO LA TABLA DE 
VALORES DE CORRIENTE DE LAS TABLAS 
430-52,430-249 O 430-250
PARA LA BOMBA CONTRA INCENDIOS SE TOMO EL 
ARTICULO 695
LA PUESTA TIERRA SE TOMO DE LA TABLA 250-122
TRANSFORMA
DOR TIPO 
PEDESTAL EN 
FACHADA DE 
250KVA
3F-4H
220/127V
No. SERIE : 
IS50-10
TERMOAGNETICO
PRINCIPAL 
QO380
 3X80A
In=59
220V
GABINETE PARA ITM 
P1200FMX
TABLERO PRINCIPAL 
 NF303AB62*
DE 6000A 
3F-4H
PARA 30 CIRCUTOS 
MONOFASICOS
DOBLE TIRO , 
SIN FUSIBLE 
SQUAR-D
 92345
400A
TERMOMAGNETICO
PRINCIPAL
 LAL26300 
 3X300A
In=277
220V
CABLE XHHW-2
250KCMIL
126,7 MM2
290A
L=10
%e=.4
3F-4H
CABLE XHHW-2
250KCMIL
126,7 MM2
290A
L=5
%e=.02
3F-3H
CABLE XHHW-2
6 AWG
13,30 MM2
75A
L=20
%e=1.5%
3F-3H
CABLE XHHW-2
10 AWG
5,260 MM2
40A
L=20
%e=1.4%
2F-2H
CABLE XHHW-2
250KCMIL
126,7 MM2
290A
L=5
%e=.02
CABLE XHHW-2
250KCMIL
126,7 MM2
290A
L=5
%e=.02
In=366A
Ic=456.32A
3F-4H
L=10
%e=0.3%
CABLE XHHW-2 600V
600KCMIL
304,0 MM2
TABLERO
BARILLA DE TIERRA
MOTOR
TERMOMAGNETICO
DOBLE TIRO
SIMBOLOGIA
M
TRANSFORMADOR
EMPRESA :DEL CARMEN
COMPAÑIA ELECTRICA: INSTALACIONES JC 
REALIZADOR DEL PROYECTO :SERGIO JUAREZ CORREA 
FECHA :20/05/2020
FECHA DE ACTUALIZACION DEL PLANO :------------
TELEFONO: 3310630837
CONTACTO : INSTALACIONES.JC@GMAIL.COM